Technical data
16.2 Technical specifications of CPU 410E (6ES7410-5HM08-0AB0)
CPU 410 Process Automation/CPU 410 SMART
268 System Manual, 05/2017, A5E31622160-AC
Article number
6ES7410-5HM08-0AB0
Redundant subnetworks
Yes
Change of IP address at runtime, supported
No
Number of connection resources
120
Interface types
Number of ports
2
integrated switch
Yes
Media redundancy
supported
Yes
Switchover time on line break, typ.
< 200 ms
Number of stations in the ring, max.
50
Functionality
PROFINET IO Controller
Yes
PROFINET IO Device
No
PROFINET CBA
No
Open IE communication
Yes
Web server
No
PROFINET IO Controller
Transmission rate, max.
100 Mbit/s
Services
PG/OP communication
Yes
S7 routing
Yes
S7 communication
Yes
Open IE communication
Yes
Shared device
No; however, usable as part of S7
Prioritized startup
No
Number of connectable IO Devices,
max.
250
Number of connectable IO Devices for
RT, max.
250
of which in line, max.
250
Activation/deactivation of IO Devices
Yes; Single mode only
IO Devices changing during operation
(partner ports), supported
No
Device replacement without swap me-
dium
Yes
Send cycles
250 µs, 500 µs, 1 ms, 2 ms, 4 ms
Updating time
250 µs to 512 ms, minimum value depends on
the number of configured user data and the con-
figured single or redundant mode

Table of Contents