EasyManuals Logo
Home>Siemens>Control Unit>SIMATIC CPU 410

Siemens SIMATIC CPU 410 User Manual

Siemens SIMATIC CPU 410
434 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #284 background imageLoading...
Page #284 background image
Properties and technical specifications of CPU 410 SMART
17.1 CPU 410 SMART
CPU 410 Process Automation/CPU 410 SMART
284 System Manual, 05/2017, A5E31622160-AC
Memory configuration
The integrated main memory of the CPU 410 SMART is 8 MB; 4 MB for programs and 4 MB
for data. This size of the load memory is 48 MB.
Time-delay interrupt OBs
The CPU 410 SMART does not support any delay alarm OBs (OB 2x) or any associated
SFCs 32, 33 and 34. If you call one of these SFCs in the user program, it is not executed. An
error message is created instead and OB 121 is called.
If a SFC is assigned to a time-delay interrupt and downloaded to the CPU 410 SMART, the
SFC is not executed. An OB request error is reported when the configured time has elapsed.
Cyclic interrupts
The CPU 410 SMART supports the following cyclic interrupt OBs:
OB 32 with a default run time of 2000 ms
OB 33 with a default run time of 1000 ms
OB 34 with a default run time of 500 ms
OB 35 with a default run time of 200 ms
You cannot set a phase offset.
Hardware interrupt OBs
The CPU 410 SMART does not support hardware interrupt OBs (OB 4x). If you assign a
SFC to a hardware interrupt and download it to the CPU 410 SMART, the SFC is ignored.
If you have nevertheless enabled hardware interrupts on I/O modules with interrupt capability
and a hardware interrupt is generated, it is merely entered in the diagnostics buffer and the
SFC is not executed.
See also
AS 410 modular systems
(http://support.automation.siemens.com/WW/view/en/77430465/130000)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals