Properties and technical specifications of CPU 410 SMART
17.2 Technical specifications of the CPU 410 SMART; (6ES7 410-5HN08-0AB0)
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
287
Article number
6ES7410-5HN08-0AB0
Address area
I/O address area
• Inputs
16 kbyte
• Outputs
16 kbyte
of which distributed
– DP interface, inputs
1 536 byte; Up to 1 500 IOs (channels)
– DP interface, outputs
1 536 byte; Up to 1 500 IOs (channels)
– PROFINET interface, inputs
1 536 byte; Up to 1 500 IOs (channels)
– PROFINET interface, outputs
1 536 byte; Up to 1 500 IOs (channels)
Digital channels
• Inputs
36 864; max.
• Outputs
36 864; max.
Analog channels
• Inputs
2 304; max.
• Outputs
2 304; max.
Hardware configuration
connectable OPs
119
Multicomputing
No
Number of DP masters
• integrated
1
• via CP
0
Number of IO Controllers
• integrated
2
• via CP
0
Number of operable FMs and CPs (recommend-
ed)
• CP, LAN
4
Slots
• required slots
2
Time of day
Clock
• Hardware clock (real-time)
Yes
• retentive and synchronizable
Yes
• Resolution
1 ms
• Deviation per day (buffered), max.
1.7 s; Power off
• Deviation per day (unbuffered), max.
8.6 s; Power on

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals