I/O configuration variants
6.1 Stand-alone operation
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
57
If you later want to expand the CPU 410 to a fault-tolerant system, proceed as follows:
1. Open a new project and insert a fault-tolerant station.
2. Copy the entire rack from the standard SIMATIC-400 station and insert it twice into the
fault-tolerant station.
3. Insert the required subnets and IO devices.
4. Copy the DP slaves from the old stand-alone operation project to the fault-tolerant station
as required.
5. Reconfigure the communication connections.
6. Carry out all changes required, such as the insertion of one-sided I/O.
For information on how to configure the project, refer to the online help.
Changing the operating mode of a CPU 410
To change the operating mode of a CPU 410, you proceed differently depending on which
operating mode you want to change to and which rack number was configured for the CPU:
Change from stand-alone to redundant operation, rack number 0
1. Insert the synchronization modules into the CPU.
2. Carry out a CPU memory reset or load a project to the CPU in which the CPU is
configured for redundant operation.
3. Insert the synchronization cables into the synchronization modules.
Change from stand-alone mode to redundant operation, rack number 1
1. Set rack number 1 on the CPU.
2. Install the CPU.
3. Carry out a CPU memory reset.
4. Insert the synchronization modules into the CPU.
5. Insert the synchronization cables into the synchronization modules.
Changing from redundant to stand-alone operation
1. Remove the CPU.
2. Remove the synchronization modules.
3. Set rack number 0 on the CPU.
4. Install the CPU.
5. Download a project to the CPU in which the CPU is configured for stand-alone operation.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals