Maintenance and service
7.11 Saving data and updating the IM 153-4 PN
ET 200M
126 Operating Instructions, 12/2008, EWA-4NEB780600602-08
Principle
An update is possible with IM 153-4 PN as of order number 6ES7153-4AA00-0XB0. For this
you require
STEP 7
V5.4 SP 2 or higher.
There are two ways of updating:
from PG/PC via PROFINET IO (direct)
viaSIMATIC Micro Memory Card
After a successful update, the former version of the IM 153-4 PN firmware must be covered
over with a sticker showing the updated version of the firmware.
Requirements
Update via PROFINET IO
The IM 153-4 PN in the station that is to be updated must be available online.
The files with the current (new) version of the firmware must be available in the file
system of your PD / PC.
for update via SIMATIC Micro Memory Card
The update files must be available on the SIMATIC Micro Memory Card.
NOTICE
When the firmware is updated, the stations in a line can fail.
Note
A firmware update with SIMATIC Micro Memory Card is not possible for interface modules
that were started with the "Prioritized startup" parameter.