EasyManua.ls Logo

Siemens SIMATIC ET 200M - 10.4 Technical specifications of the IM 153-4 PN interface module

Siemens SIMATIC ET 200M
274 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specifications
10.4 Technical specifications of the IM 153-4 PN interface module
ET 200M
234 Operating Instructions, 12/2008, EWA-4NEB780600602-08
10.4 Technical specifications of the IM 153-4 PN interface module
Order Number
6ES7153-4AA01-0XB0
Properties
The IM 153-4 PN interface module has the following properties:
● It interconnects the ET 200M with PROFINET IO.
● A maximum of 12 modules can be operated with the IM 153-4 PN
● It prepares the data for the inserted modules.
The following settings can be made: SM, CP, non-assignable FM
● It supplies the backplane bus
● Integrated switch with 2 ports
● Transfer and backup of the device name on SIMATIC Micro Memory Card
● Firmware update using a SIMATIC Micro Memory Card or PROFINET IO
● The reference potential M of the rated supply voltage of the IM 153-4 PN to the rail
(protective conductor) is connected by means of an RC combination, thus permitting an
ungrounded configuration
● Supported Ethernet services
– ping
– arp
– Network diagnostics (SNMP): LLDP-MIB / MIB-2
– Resetting SNMP parameters to the factory settings
– I&M data
● Interrupts
– Diagnostic interrupts
– Hardware interrupts
– Removal / insertion interrupts
– Maintenance interrupts
● Port diagnostics
● Port disabling
● Support for real-time communication (RT Class 1 and Class 2).
● Maximum address space of 200 bytes I/O data.
● Data records for I/O modules
● As of 6ES7153-4AA01-0XB0:
– Isochronous real-time communication
–
Minimum updating time 250 μs with IRT
– Prioritized star
tup
– Device replacement without removable media / programming device
– Changing IO devices during operation (changing partner ports)