Programming
5.3 System function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
28 Manual, 06/2019, A5E46959434-AA
Parameter
Decla-
ration
Data
type
Memory
area
Description
EVENT_S
CHEME
USInt I, Q, M,
D, L
Event characterization that identifies the source of the event:
0~4: Normal event message
255: Power cycle event
Scheme of the
event
0 1 2 3 4 255
EVENT_S
RC_1
USInt I, Q, M,
D, L
First event
source infor-
mation
Instance
type
Short
address
Short
ad-
dress
Device
group
In-
stance
group
Group
1
EVENT_S
RC_2
USInt I, Q, M,
D, L
Second event
source infor-
mation
Instance
number
Instance
type
In-
stance
number
In-
stance
type
In-
stance
type
Short
ad-
dress
2
EVENT_I
NFO
WORD I, Q, M,
D, L
When EVENT_SCHEME ≤ 4, the lower 10 bits of EVENT_INFO indicate the
event data.
When EVENT_SCHEME = 255, EVENT_INFO shows "16#0000".
For the detailed meaning of EVENT_INFO in DALI standard, refer to the
following section "Parameter EVENT_INFO".
RSV_MS
G
BOOL I, Q, M,
D, L
The status of the reserved message. When the CM 1xDALI receives a re-
served message, the RSV_MSG remains true for one cycle:
RSV_MSG = 0: No reserved message
RSV_MSG = 1: A reserved message is received.
RSV_MS
G_LEN
USInt I, Q, M,
D, L
The bit length of the reserved message
RSV_MS
G_VAL
DWORD I, Q, M,
D, L
The bit stream of the reserved message
1
For a valid device group, group of EVENT_SRC_1 indicates the lowest group; otherwise it shows "16#FF".
2
For a valid short address, short address of EVENT_SRC_2 indicates the short address of the device; oth-
erwise, it shows "16#FF".
Parameter CM_STATUS
Each Bit of the CM_STATUS indicates the different status:
Bit
Explanation of status
Bit 0
The CM 1xDALI is initializing.
Bit 1
The CM 1xDALI is set to quiescent mode by DALI command "START QUIESCENT MODE".
Bit 2
The CM 1xDALI is disabled by DALI command "DISABLE APPLICATION CONTROLLER".
3
Bit 3
The application controller is disabled by module parameters.
4
Bit 4
The DALI bus is over voltage.
Bit 5
Missing Voltage (MV)
5
of module input
Bit 6
The DALI bus is short-circuited.
Bit 7 Integrated DALI bus power is disabled in CM 1xDALI, and there is no external DALI bus power on DALI
bus.