User data variants
D.1 User data variants with 32 bytes input data / 12 bytes output data
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
138 Manual, 12/2015, A5E36061895-AA
Reactive power L1L2L3 (ID 252 or FC
H
)
Table D- 4 Reactive power L1L2L3
Byte
Allocation
Data type
Unit
Value range
Measured
value ID
0
User data variant
BYTE
-
252 (FC
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit string qq xx xx xx -
2 ... 3
Current L1
UINT
1 mA
0 … 65535
66007
4 ... 5
Current L2
UINT
1 mA
0 … 65535
66008
6 ... 7
Current L3
UINT
1 mA
0 … 65535
66009
8 ... 9
Reactive power L1
INT
1 var
-27648 … 27648
66016
10 ... 11
Reactive power L2
INT
1 var
-27648 … 27648
66017
12 ... 13
Reactive power L3
INT
1 var
-27648 … 27648
66018
14 ... 15
Total reactive power L1L2L3
INT
1 var
-27648 … 27648
66036
16 ... 19
Total reactive energy L1L2L3
UDINT
1 varh
0 ... 4294967295
226
20
Power factor L1
USINT
0.01
0 … 100
66019
21
Power factor L2
USINT
0.01
0 … 100
66020
22
Power factor L3
USINT
0.01
0 … 100
66021
23
Total power factor L1L2L3
USINT
0.01
0 … 100
66037
24
Scaling current L1
USINT
-
0 ... 255
-
25
Scaling current L2
USINT
-
0 ... 255
-
26
Scaling current L3
USINT
-
0 ... 255
-
27
Scaling reactive power L1
USINT
-
0 ... 255
-
28
Scaling reactive power L2
USINT
-
0 ... 255
-
29
Scaling reactive power L3
USINT
-
0 ... 255
-
30 Scaling reactive power L1L2L3 USINT - 0 ... 255 -
31