Energy counters
7.5 Data record for energy counter (DS 143)
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
55
7.5
Data record for energy counter (DS 143)
7.5.1
Structure for energy counters (DS 143)
Energy meter data record 143 for different actions
The energy meter data record 143 includes all energy meters available on the module
phase-by-phase. The data record can be used for different actions:
Reset the energy counter to user-specific value (e.g. "0")
Reading the current values of the energy counters
Reading the overflow counters
Reading the operating hours
Energy meter data record 143
Table 7- 1 Energy meter data record 143
Byte
Measured variable
Data type
Unit
Value range
Measured
value ID
0
Version
BYTE
-
1
-
1 Reserved BYTE - 0 -
2
Status / control byte 1 - L1
BYTE
Bit string
-
-
3 Status / control byte 2 - L1 BYTE Bit string
4
Status / control byte 1 - L2
BYTE
Bit string
5
Status / control byte 2 - L2
BYTE
Bit string
6
Status / control byte 1 - L3
BYTE
Bit string
7
Status / control byte 2 - L3
BYTE
Bit string
8...15
Active energy inflow (initial value) L1
LREAL
Wh
During reading:
0.0...1.8 x 10
308
During writing
For continuous counting:
0.0...3.4 x 10
12
During writing
For periodic counting:
0...configured full-scale
value (10
3
...10
15
)
61180
16...23
Active energy outflow (initial value) L1
LREAL
Wh
61181
24...31
Reactive energy inflow (initial value) L1
LREAL
varh
61182
32...39
Reactive energy outflow (initial value) L1
LREAL
varh
61183
40...47
Apparent energy (initial value) L1
LREAL
VAh
61184
48...55
Active energy inflow (initial value) L2
LREAL
Wh
61200
56...63
Active energy outflow (initial value) L2
LREAL
Wh
61201
64...61
Reactive energy inflow (initial value) L2
LREAL
varh
61202
72...79
Reactive energy outflow (initial value) L2
LREAL
varh
61203
80...87
Apparent energy (initial value) L2
LREAL
VAh
61204
88...95
Active energy inflow (initial value) L3
LREAL
Wh
61220
96...103
Active energy outflow (initial value) L3
LREAL
Wh
61221
104...111 Reactive energy inflow (initial value) L3 LREAL varh 61222
112...119
Reactive energy outflow (initial value) L3
LREAL
varh
61223
120...127
Apparent energy (initial value) L3
LREAL
VAh
61224

Table of Contents