Measured value data records
E.9 Measured value data record for advanced measurement and status values (DS 150)
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
170 Manual, 12/2015, A5E36061895-AA
Byte
Measured variable
For-
mat
Unit
Value range
Meas-
ured
value
ID
Connection type
1P2W
3x1P2W
2P3W
3P4W
3P4W1
80...83 Min. voltage UL1-N REA
L
V 0.0 ... 1000000.0 72
84...87 Min. current L3 REA
L
A 0.0 ... 100000.0 78
88...91 Min. apparent
power L3
REA
L
VA -3.0 x 10
9
+3.0 x 10
9
81
92...95 Min. active
power L3
REA
L
W -3.0 x 10
9
+3.0 x 10
9
85
96...99 Min. reactive pow-
er L3
REA
L
var -3.0 x 10
9
+3.0 x 10
9
87
100...103 Min. power
factor L3
REA
L
- 0.0 ... 1.0 90
E.9
Measured value data record for advanced measurement and status
values (DS 150)
Measured variables of the module
Data record 150
Byte
Measured variable
Format
Unit
Value range
Measured
value ID
0
Version
BYTE
-
1
-
1
Reserved
BYTE
-
0
-
2...5
Operating hours counter L1L2L3
REAL
h
0.0 ... 3.4 x 10
38
65504
6...9
Operating hours counter L1
REAL
h
0.0 ... 3.4 x 10
38
65505
10...13
Operating hours counter L2
REAL
h
0.0 ... 3.4 x 10
38
65506
14...17
Operating hours counter L3
REAL
h
0.0 ... 3.4 x 10
38
65507
18...19
Status limit violation GW 1...16
WORD
Bit string
xxxx xxxx xxxx xxxx
65509
20...21
Status of energy counter overflows
1
WORD
Bit string
xxxx xxxx xxxx xxxx
65508
22...25
Counter limit violation GW 1
UDINT
-
0 ... 4294967296
65510
26...29
Counter limit violation GW 2
UDINT
-
0 ... 4294967296
65511
30...33 Counter limit violation GW 3 UDINT - 0 ... 4294967296 65512
34...37
Counter limit violation GW 4
UDINT
-
0 ... 4294967296
65513
38...41 Counter limit violation GW 5 UDINT - 0 ... 4294967296 65514
42...45
Counter limit violation GW 6
UDINT
-
0 ... 4294967296
65515
46...49
Counter limit violation GW 7
UDINT
-
0 ... 4294967296
65516
50...53
Counter limit violation GW 8
UDINT
-
0 ... 4294967296
65517
54...57
Counter limit violation GW 9
UDINT
-
0 ... 4294967296
65518
58...61
Counter limit violation GW 10
UDINT
-
0 ... 4294967296
65519

Table of Contents

Other manuals for Siemens simatic et200sp

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic et200sp and is the answer not in the manual?

Siemens simatic et200sp Specifications

General IconGeneral
CategoryI/O Systems
Power Supply24 V DC
Protection RatingIP20
Number of ModulesUp to 64 modules
MountingDIN Rail
Communication ProtocolsPROFINET, PROFIBUS
Storage Temperature-40 °C to +70 °C
Digital InputsYes (depending on module)
Digital OutputsYes (depending on module)
Analog InputsYes (depending on module)
Analog OutputsYes (depending on module)
ModularityModular
Relative Humidity5 to 95% (non-condensing)
WeightVaries by configuration
System TypeDistributed I/O