Measured value data records
E.8 Measured value data record for phase-based measured values L3 (DS 149)
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
169
Measured value data record for phase-based measured values L3
(DS 149)
Measured variables of the module (DS 149)
0 Version BYT
- 1 - ✓ ✓ ✓ ✓ ✓
1 Reserved BYT
E
- 0 - ✓ ✓ ✓ ✓ ✓
2...3 Qualifier L3 WO
RD
Bit
field
0b 00 00 00 00
65502 ✓ ✓ ✓
4...7 Voltage UL1-N REA
V 0.0 ... 1000000.0 3 ✓ ✓ ✓
8...11 Current L3 REA
A 0.0 … 100000.0 9 ✓ ✓ ✓
12...15 Apparent power L3 REA
VA -3.0 x 10
9
…
9
12 ✓ ✓ ✓
16...19 Active power L3 REA
W -3.0 x 10
9
…
9
15 ✓ ✓ ✓
20...23 Reactive power L3 REA
var -3.0 x 10
9
…
9
18 ✓ ✓ ✓
24...27 Power factor L3 REA
- 0.0 ... 1.0 21 ✓ ✓ ✓
28...31 Phase angle L3 REA
° 0.0 ... 360.0 61218 ✓ ✓ ✓
32...39 Apparent energy
L3
LRE
AL
VAh 0.0 ... 1.8 x 10
308
61224 ✓ ✓ ✓
40...47 Active energy
LRE
Wh 0.0 ... 1.8 x 10
308
61225 ✓ ✓ ✓
48...55 Reactive energy
(total) L3
LRE
AL
varh 0.0 ... 1.8 x 10
308
61226 ✓ ✓ ✓
56...59 Max. voltage
REA
V 0.0 ... 1000000.0 42 ✓ ✓ ✓
60...63 Max. current L3 REA
A 0.0 ... 100000.0 48 ✓ ✓ ✓
64...67 Max. apparent
REA
VA -3.0 x 10
9
…
9
51 ✓ ✓ ✓
68...71 Max. active power
REA
W -3.0 x 10
9
…
9
53 ✓ ✓ ✓
72...75 Max. reactive pow-
REA
var -3.0 x 10
9
…
9
57 ✓ ✓ ✓
76...79 Max. power
REA
- 0.0 ... 1.0 60 ✓ ✓ ✓