Measured value data records
E.6 Measured value data record for phase-based measured values L1 (DS 147)
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
166 Manual, 12/2015, A5E36061895-AA
Byte
Measured variable
Format
Unit
Default
Measured
value ID
Connection type
1P2W
3x1P2W
2P3W
3P4W
3P4W1
66...69 Min. reactive power
L2
REAL var +3.0 x 10
9
86
70...73 Min. reactive power
L3
REAL var +3.0 x 10
9
87
74...77 Min. power factor L1 REAL - 1 88
78...81
Min. power factor L2
REAL
-
1
89
82...85
Min. power factor L3
REAL
-
1
90
86...89
Min. frequency
REAL
Hz
65
91
90...93 Min. total apparent
power
REAL VA +3.0 x 10
9
95
94...97 Min. total active pow-
er
REAL W +3.0 x 10
9
96
98...101 Min. total reactive
power
REAL var +3.0 x 10
9
97
102 Min. total power fac-
tor
REAL - 1 98
1
The values reference the amount of the current measured value
E.6
Measured value data record for phase-based measured values L1
(DS 147)
Measured variables of the module (DS 147)
Byte
Measured varia-
ble
Format
Unit
Value range
Meas-
ured
value
ID
Connection type
1P2W
3x1P2W
2P3W
3P4W
3P4W1
0
Version
BYTE
-
1
-
1
Reserved
BYTE
-
0
-
2...3 Qualifier L1 WORD Bit field 0b 00 00 00 00
0b qq 00 00 xx
65500
4...7
Voltage UL1-N
REAL
V
0.0 ... 1000000.0
1
8...11
Current L1
REAL
A
0.0 … 100000.0
7
12...15 Apparent
power L1
REAL VA -3.0 x 10
9
+3.0 x 10
9
10
16...19 Active power L1 REAL W -3.0 x 10
9
+3.0 x 10
9
13
20...23 Reactive
power L1
REAL var -3.0 x 10
9
+3.0 x 10
9
16
24...27
Power factor L1
REAL
-
0.0 ... 1.0
19