EasyManuals Logo

Siemens simatic et200sp User Manual

Siemens simatic et200sp
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #166 background imageLoading...
Page #166 background image
Measured value data records
E.6 Measured value data record for phase-based measured values L1 (DS 147)
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
166 Manual, 12/2015, A5E36061895-AA
Byte
Measured variable
Format
Unit
Default
Measured
value ID
Connection type
1P2W
3x1P2W
2P3W
3P4W
3P4W1
66...69 Min. reactive power
L2
REAL var +3.0 x 10
9
86
70...73 Min. reactive power
L3
REAL var +3.0 x 10
9
87
74...77 Min. power factor L1 REAL - 1 88
78...81
Min. power factor L2
REAL
-
1
89
82...85
Min. power factor L3
REAL
-
1
90
86...89
Min. frequency
REAL
Hz
65
91
90...93 Min. total apparent
power
REAL VA +3.0 x 10
9
95
94...97 Min. total active pow-
er
REAL W +3.0 x 10
9
96
98...101 Min. total reactive
power
REAL var +3.0 x 10
9
97
102 Min. total power fac-
tor
REAL - 1 98
1
The values reference the amount of the current measured value
E.6
Measured value data record for phase-based measured values L1
(DS 147)
Measured variables of the module (DS 147)
Byte
Measured varia-
ble
Format
Unit
Value range
Meas-
ured
value
ID
Connection type
1P2W
3x1P2W
2P3W
3P4W
3P4W1
0
Version
BYTE
-
1
-
1
Reserved
BYTE
-
0
-
2...3 Qualifier L1 WORD Bit field 0b 00 00 00 00
0b qq 00 00 xx
65500
4...7
Voltage UL1-N
REAL
V
0.0 ... 1000000.0
1
8...11
Current L1
REAL
A
0.0 … 100000.0
7
12...15 Apparent
power L1
REAL VA -3.0 x 10
9
+3.0 x 10
9
10
16...19 Active power L1 REAL W -3.0 x 10
9
+3.0 x 10
9
13
20...23 Reactive
power L1
REAL var -3.0 x 10
9
+3.0 x 10
9
16
24...27
Power factor L1
REAL
-
0.0 ... 1.0
19

Table of Contents

Other manuals for Siemens simatic et200sp

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic et200sp and is the answer not in the manual?

Siemens simatic et200sp Specifications

General IconGeneral
CategoryI/O Systems
Power Supply24 V DC
Protection RatingIP20
Number of ModulesUp to 64 modules
MountingDIN Rail
Communication ProtocolsPROFINET, PROFIBUS
Storage Temperature-40 °C to +70 °C
Digital InputsYes (depending on module)
Digital OutputsYes (depending on module)
Analog InputsYes (depending on module)
Analog OutputsYes (depending on module)
ModularityModular
Relative Humidity5 to 95% (non-condensing)
WeightVaries by configuration
System TypeDistributed I/O

Related product manuals