EasyManua.ls Logo

Siemens simatic et200sp - Measured Value Data Record for Phase-Based Measured Values L2 (DS 148)

Siemens simatic et200sp
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Measured value data records
E.7 Measured value data record for phase-based measured values L2 (DS 148)
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
167
Byte
Measured varia-
ble
Format
Unit
Value range
Meas-
ured
value
ID
Connection type
1P2W
3x1P2W
2P3W
3P4W
3P4W1
28...31
Phase angle L1
REAL
°
0.0 ... 360.0
61178
32...39 Apparent
energy L1
LREAL VAh 0.0 ... 1.8 x 10
308
61184
40...47 Active energy
(total) L1
LREAL Wh 0.0 ... 1.8 x 10
308
61185
48...55 Reactive energy
(total) L1
LREAL varh 0.0 ... 1.8 x 10
308
61186
56...59 Max. voltage
UL1-N
REAL V 0.0 ... 1000000.0 40
60...63
Max. current L1
REAL
A
0.0 ... 100000.0
46
64...67 Max. apparent
power L1
REAL VA -3.0 x 10
9
+3.0 x 10
9
49
68...71 Max. active
power L1
REAL W -3.0 x 10
9
+3.0 x 10
9
52
72...75 Max. reactive
power L1
REAL var -3.0 x 10
9
+3.0 x 10
9
55
76...79 Max. power
factor L1
REAL - 0.0 ... 1.0 58
80...83 Min. voltage
UL1-N
REAL V 0.0 ... 1000000.0 70
84...87
Min. current L1
REAL
A
0.0 ... 100000.0
76
88...91 Min. apparent
power L1
REAL VA -3.0 x 10
9
+3.0 x 10
9
79
92...95 Min. active pow-
er L1
REAL W -3.0 x 10
9
+3.0 x 10
9
83
96...99 Min. reactive
power L1
REAL var -3.0 x 10
9
+3.0 x 10
9
85
100...103 Min. power
factor L1
REAL - 0.0 ... 1.0 88
E.7
Measured value data record for phase-based measured values L2
(DS 148)
Measured variables of the module (DS 148)
Byte
Measured varia-
ble
Format
Unit
Value range
Meas-
ured
value
ID
Connection type
1P2W
3x1P2W
2P3W
3P4W
3P4W1
0
Version
BYTE
-
1
-
1
Reserved
BYTE
-
0
-

Table of Contents