EasyManua.ls Logo

Siemens simatic et200sp - Module Version 32 I; 12 Q

Siemens simatic et200sp
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Module versions
C.2 Module version "32 I / 12 Q"
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
125
C.2
Module version "32 I / 12 Q"
User data of the module
The module occupies 32 bytes of input user data and 12 bytes of output user data. Of these
the module uses 2 bytes input data for status information and 12 bytes output data for
control information. Measured variables can be read cyclically via user data (Bytes 2 to 31)
or acyclically via measured value data records
Structure of input user data
You can set the contents of the input user data dynamically. You can choose between
different user data variants.
Table C- 3 Structure of input user data (12 bytes)
Byte
Validity
Designation
Comment
0 Module User data vari-
ant
-
1 Module Quality infor-
mation
Quality bits to describe the quality of the basic measured values
2 ... 31 Module or phase Data 2 or 4 bytes of measured values or calculated values according to
user data variant

Table of Contents

Other manuals for Siemens simatic et200sp

Related product manuals