User data variants
D.1 User data variants with 32 bytes input data / 12 bytes output data
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
153
Basic variables phase-specific measurement (ID 155 or 9B
H
)
Table D- 22 Basic variables phase-specific measurement L3
Byte
Allocation
Data type
Unit
Value range
Measured
value ID
0
User data variant
BYTE
-
155 (9B
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit string qq xx xx xx -
2 ... 3
Current L3
UINT
1 mA
0 … 65535
66009
4 ... 5
Voltage UL3-N
UINT
0.01 V
0 … 65535
66003
6 ... 7
Active power L3
INT
1 W
-27648 … 27648
66015
8 ... 9
Reactive power L3
INT
1 var
-27648 … 27648
66018
10 ... 11
Apparent power L3
INT
1 VA
-27648 … 27648
66012
12 ... 15
Active energy L3 total (inflow - outflow)
UDINT
1 Wh
0 … 4294967295
62315
16 ... 19
Reactive energy L3 total (inflow - outflow)
UDINT
1 varh
0 … 4294967295
62316
20 ... 23
Apparent energy L3
UDINT
1 VAh
0 … 4294967295
62314
24
Scaling current L3
USINT
-
0 ... 255
-
25
Scaling active power L3
USINT
-
0 ... 255
-
26
Scaling reactive power L3
USINT
-
0 ... 255
-
27
Scaling apparent power L3
USINT
-
0 ... 255
-
28
Scaling active energy L3 total (inflow - outflow)
USINT
-
0 ... 255
-
29
Scaling reactive energy L3 total (inflow - outflow)
USINT
-
0 ... 255
-
30
Scaling apparent energy L3
USINT
-
0 ... 255
-
31
Power factor L3
USINT
0.01
0 … 100
66021

Table of Contents

Other manuals for Siemens simatic et200sp

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic et200sp and is the answer not in the manual?

Siemens simatic et200sp Specifications

General IconGeneral
CategoryI/O Systems
Power Supply24 V DC
Protection RatingIP20
Number of ModulesUp to 64 modules
MountingDIN Rail
Communication ProtocolsPROFINET, PROFIBUS
Storage Temperature-40 °C to +70 °C
Digital InputsYes (depending on module)
Digital OutputsYes (depending on module)
Analog InputsYes (depending on module)
Analog OutputsYes (depending on module)
ModularityModular
Relative Humidity5 to 95% (non-condensing)
WeightVaries by configuration
System TypeDistributed I/O