EasyManua.ls Logo

Siemens simatic et200sp - Page 153

Siemens simatic et200sp
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User data variants
D.1 User data variants with 32 bytes input data / 12 bytes output data
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
153
Basic variables phase-specific measurement (ID 155 or 9B
H
)
Table D- 22 Basic variables phase-specific measurement L3
Byte
Allocation
Data type
Unit
Value range
Measured
value ID
0
User data variant
BYTE
-
155 (9B
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit string qq xx xx xx -
2 ... 3
Current L3
UINT
1 mA
0 … 65535
66009
4 ... 5
Voltage UL3-N
UINT
0.01 V
0 … 65535
66003
6 ... 7
Active power L3
INT
1 W
-27648 … 27648
66015
8 ... 9
Reactive power L3
INT
1 var
-27648 … 27648
66018
10 ... 11
Apparent power L3
INT
1 VA
-27648 … 27648
66012
12 ... 15
Active energy L3 total (inflow - outflow)
UDINT
1 Wh
0 … 4294967295
62315
16 ... 19
Reactive energy L3 total (inflow - outflow)
UDINT
1 varh
0 … 4294967295
62316
20 ... 23
Apparent energy L3
UDINT
1 VAh
0 … 4294967295
62314
24
Scaling current L3
USINT
-
0 ... 255
-
25
Scaling active power L3
USINT
-
0 ... 255
-
26
Scaling reactive power L3
USINT
-
0 ... 255
-
27
Scaling apparent power L3
USINT
-
0 ... 255
-
28
Scaling active energy L3 total (inflow - outflow)
USINT
-
0 ... 255
-
29
Scaling reactive energy L3 total (inflow - outflow)
USINT
-
0 ... 255
-
30
Scaling apparent energy L3
USINT
-
0 ... 255
-
31
Power factor L3
USINT
0.01
0 … 100
66021

Table of Contents

Other manuals for Siemens simatic et200sp

Related product manuals