EasyManuals Logo

Siemens simatic et200sp User Manual

Siemens simatic et200sp
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #83 background imageLoading...
Page #83 background image
Parameters
12.2 Description of parameters
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
83
Operating hours counter
Enable the operating hours counter here. The counting starts from a programmable
minimum current value. The counter can be reset or pre-defined using data record or output
bit.
Enable gate of operating hours counter
Enable the gate for the operating hours counter here. When the gate is activated, the
operating hours counter only counts when the corresponding output data bit (DQ bit) is set to
"1".
Current transformer primary current
Enter here the nominal value for the primary current of the current transformer used. The
transformer ratio is calculated from the primary and secondary current.
Current transformer secondary current
Enter here the nominal value for the secondary current (1 A or 5 A) of the current
transformer used. The transformer ratio is calculated from the primary and secondary
current.
Voltage transformer primary voltage
To determine the voltage transformer ratio, enter the primary voltage here. The transformer
ratio is calculated from the primary and secondary voltage.
Voltage transformer secondary voltage
Enter the secondary voltage to determine the voltage transformer ratio here. The transformer
ratio is calculated from the primary and secondary voltage.
Reverse current direction
Setting to determine whether or not to reverse the direction of current.
In the event of inadvertent incorrect connection, this parameter can be used to correct the
measured values, thus saving the hassle of rewiring. The direction of the current is only
evident from the power measurement values. The current measurement value is an rms
value.
Number of limits
Enter the number of measured values that you want to monitor for limits.

Table of Contents

Other manuals for Siemens simatic et200sp

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic et200sp and is the answer not in the manual?

Siemens simatic et200sp Specifications

General IconGeneral
CategoryI/O Systems
Power Supply24 V DC
Protection RatingIP20
Number of ModulesUp to 64 modules
MountingDIN Rail
Communication ProtocolsPROFINET, PROFIBUS
Storage Temperature-40 °C to +70 °C
Digital InputsYes (depending on module)
Digital OutputsYes (depending on module)
Analog InputsYes (depending on module)
Analog OutputsYes (depending on module)
ModularityModular
Relative Humidity5 to 95% (non-condensing)
WeightVaries by configuration
System TypeDistributed I/O