Setting parameters for blocks
3.5 Programming the Ident profile
Ident profile and Ident blocks, standard function for Ident systems
Function Manual, 10/2018, C79000-G8976-C387-04
95
Normal transmit power
1)
Reduced output power
0x05 = 0.5 m
0x0A = 1.0 m
0x0F = 1.5 m
0x14 = 2.0 m
0x19 = 2.5 m
0x1E = 3.0 m
0x23 = 3.5 m
0x85
0x8A
0x8F
0x91
0x99
0x9E
0xA3
Set reduced transmit power when several
readers are positioned close together or
when transponders which are located in
the vicinity of a reader are detected later
or no longer.
Disadvantage: The field lobe becomes
smaller and there is less time for commu-
nication or positioning must be more
Intermediate values in steps of 0.1 m are possible (0x02, 0x03, ..., 0x23)
MOBY D Transmit power from 0.5 W to 10 W in increments of 0.25 W
Only effective with SLG D10S; a power of 1 W (04 hex) is set for SLG D11S /
D12S and cannot be changed.
No. of tran-
sponders
RF300 The reader is basically intended for multitag operation, which is, however, not
currently released.
Maximum number of transponders that can be processed at the same time in the
antenna field. Currently permitted values "1".
RF600 Number of transponders expected in the antenna field.
Permitted values:
• 0x01 ... 0x28 for RF620R
• 0x01 ... 0x50 for RF630R with 2 antennas (SET-ANT = 0x03)
• 0x01 ... 0x28 for RF630R with 1 antenna (SET-ANT = 0x01 or SET-ANT =
0x02).
The value specified here defines the maximum expected number of transponders
to be read (EPC-ID) in the inventory.
The value does not restrict the number of transponders to be processed in the
antenna field. To allow an efficient inventory of transponders in the antenna field,
the values given here should not deviate from the maximum number of transpond-
ers expected in the antenna field by more than approx. 10%.
field_on_
control
RF200,
RF300,
MOBY D
0x00 (reserved)