Setting parameters for blocks
3.5 Programming the Ident profile
Ident profile and Ident blocks, standard function for Ident systems
96 Function Manual, 10/2018, C79000-G8976-C387-04
RF600 "field_ON_control" sets the communications speed (fast/slow) and Tag Hold
Bit Description
0 ... 1 Speed
Reader parameter assignments that have been optimized depending on
the application are made available via the speed:
• 0x00 = Fast detection
• 0x02 = Slower, more reliable detection
5 Tag hold
• 0x00 = OFF
• 0x01 = ON
6 ScanningMode (relevant for multitag mode):
• 0x00 = Normal multitag mode without ScanningMode (including "re-
peat_command")
• 0x01 = ScanningMode
Unspecified read commands (UID = 0x00) are also accepted by the
CM/reader if there is more than one transponder in the antenna field.
By setting bit 6 to 0x01, the reader in multitag mode is prepared for
the use of "ScanningMode".
MOBY U BERO mode; automatic activation/deactivation of the antenna field. The "Antenna
ON/OFF" command is superimposed by the BERO mode.
without BEROs; no reader synchronization
0x01 One or two BEROs
The BEROs are ORed. The antenna field is turned on during the actua-
0x02 One or two BEROs
The 1st BERO switches the antenna field on and the 2nd BERO switch-
es the antenna field off. If there are two BEROs and a "field_ON_time" is
set, the antenna field is automatically turned off if the 2nd BERO does
not switch within this BERO time.
If no "field_ON_time" is set, the antenna field remains turned on until the
0x03 Activating reader synchronization over cable connection
You will find further information in the MOBY U manual for configuration,