Diagnostics
11.2 List of faults and alarms
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
397
Fault
Cause
Remedy
F7901: Motor overspeed
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
The maximumly permissible speed has
been exceeded.
The speed limit has been exceeded.
Check and correct the maximum speed
(p1082).
Check and correct the speed limit
(p29070, p29071), and the DI signals
SLIM1 and SLIM2.
Check if there are any peaks of actual
speed. If the value of the peak is especial-
ly large, contact the hotline.
F7995: Motor identification
failure
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
For incremental motor, needs pole position
identification when first SON. If the motor
already in run (i.e. by external force) posi-
tion identification may failure.
Stop the motor before servo on.
F30001: Power unit: Overcur-
rent
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
The power unit has detected an overcur-
rent condition.
Closed-loop control is incorrectly pa-
rameterized.
Controller parameters are not proper.
Motor has a short-circuit or fault to
ground (frame).
Power cables are not correctly con-
nected.
Power cables exceed the maximum
permissible length.
Power unit defective.
Line phase interrupted.
Check the motor data - if required, carry
out commissioning.
Modify speed loop Kp (p29120), position
loop Kv (p29110).
Check the motor circuit configuration
(star-delta).
Check the power cable connections.
Check the power cables for short-circuit or
ground fault.
Check the length of the power cables.
Replace power unit.
Check the line supply phases.
Check the external braking resistor con-
nection.
F30002: DC link voltage,
overvoltage
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
The power unit has detected overvoltage
in the DC link.
Motor regenerates too much energy.
Device connection voltage too high.
Line phase interrupted.
Increase the ramp-down time.
Activate the DC link voltage controller.
Use a braking resistor.
Increase the current limit of the infeed or
use a larger module.
Check the device supply voltage.
Check the line supply phases.
F30003: DC link voltage,
undervoltage
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
The power unit has detected an undervolt-
age condition in the DC link.
Line supply failure
Line supply voltage below the permis-
sible value.
Line supply infeed failed or interrupted.
Line phase interrupted.
Check the line supply voltage
Check the line supply infeed and observe
the fault messages relating to it (if there
are any)
Check the line supply phases.
Check the line supply voltage setting.