Diagnostics
11.2 List of faults and alarms
SINAMICS V90, SIMOTICS S-1FL6
398 Operating Instructions, 04/2019, A5E36037884-007
Fault
Cause
Remedy
F30004: Drive heat sink over-
temperature
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
The temperature of the power unit heat
sink has exceeded the permissible limit
value.
Insufficient cooling, fan failure.
Overload.
Surrounding temperature too high.
Pulse frequency too high.
Check whether the fan is running.
Check the fan elements.
Check whether the surrounding tempera-
ture is in the permissible range.
Check the motor load.
Reduce the pulse frequency if this is high-
er than the rated pulse frequency.
F30005: Power unit: Overload
I
2
t
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
The power unit was overloaded.
The permissible rated power unit cur-
rent was exceeded for an inadmissibly
long time.
The permissible load duty cycle was
not maintained.
Reduce the continuous load.
Adapt the load duty cycle.
Check the motor and power unit rated
currents.
F30011: Line phase failure in
main circuit
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
At the power unit, the DC link voltage rip-
ple has exceeded the permissible limit
value.
Possible causes:
A line phase has failed.
The 3 line phases are inadmissibly
unsymmetrical.
The fuse of a phase of a main circuit
has ruptured.
A motor phase has failed.
Check the main circuit fuses.
Check whether a single-phase load is
distorting the line voltages.
Check the motor feeder cables.
F30015: Phase failure motor
cable
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
A phase failure in the motor feeder cable
was detected.
The signal can also be output in the follow-
ing case:
The motor is correctly connected, however
the closed-speed control is instable and
therefore an oscillating torque is generat-
ed.
Check the motor feeder cables.
Check the speed controller settings.
F30021: Ground fault
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
Power unit has detected a ground fault.
Ground fault in the power cables.
Winding fault or ground fault at the
motor.
Check the power cable connections.
Check the motor.