Diagnostics
11.2 List of faults and alarms
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
399
Fault
Cause
Remedy
F30027: Precharging DC link
time monitoring
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
The power unit DC link was not able to
be pre-charged within the expected
time.
There is no line supply voltage con-
nected.
The line contactor/line side switch has
not been closed.
The line supply voltage is too low.
The pre-charging resistors are over-
heated as there were too many pre-
charging operations per time unit
The pre-charging resistors are over-
heated as the DC link capacitance is
too high.
The pre-charging resistors are over-
heated.
The pre-charging resistors are over-
heated as the line contactor was closed
during the DC link fast discharge
through the Braking Module.
The DC link has either a ground fault or
a short-circuit.
The pre-charging circuit is possibly
defective.
Check the line supply voltage at the input
terminals.
F30036: Internal overtemper-
ature
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
The temperature inside the drive converter
has exceeded the permissible temperature
limit.
Insufficient cooling, fan failure.
Overload.
Surrounding temperature too high.
Check whether the fan is running.
Check the fan elements.
Check whether the surrounding tempera-
ture is in the permissible range.
Notice:
This fault can only be acknowledged once the
permissible temperature limit minus 5 K has
been fallen below.
F30050: 24 V supply over-
voltage
Reaction: OFF2
Acknowledgement: POWER
ON
The voltage monitor signals an overvoltage
fault on the module.
Check the 24 V power supply.
Replace the module if necessary.
F30071: No new actual val-
ues received from the power
unit
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
The number of actual value telegrams from
the power unit that have failed has ex-
ceeded the permissible number.
Replace the module if necessary.