General information
2.7 Technical data
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
63
Product packag-
ing
Vibration 2 Hz to 9 Hz: 3.5 mm deflection
9 Hz to 200 Hz: 1 g vibration
Quantity of cycles: 10 per axis
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be
provided in accordance with the National Electrical Code and any additional local codes.
The V90 200 V servo drive has an overvoltage threshold of 410 V DC and an undervoltage threshold of 150 V DC; the
V90 400 V servo drive has an overvoltage threshold of 820 V DC and an undervoltage threshold of 320 V DC.
SINAMICS V90 does not support motor overtemperature protection. Motor overtemperature is calculated by I
2
t and
protected by the output current from the drive.
Max. supported motor power
0.1 0.2 0.4 0.75 1.0 1.5 2
Outline dimensions (W x H x
45 x 170 x 170 55 x 170 x
80 x 170 x
95 x 170 x 195
1)
Regenerative resistor (W)
Voltage/frequency
FSA, FSB and FSC: single phase/three phase 200 VAC to 240 VAC, 50/60 Hz
FSD: three phase 200 VAC to 240 VAC, 50/60 Hz
Permissible voltage fluctua-
-15% to +10%
Permissible frequency fluc-
-10% to +10%
Permissible supply configura-
TN, TT, IT
Short-circuit current (SCCR) Maximum permissible short-circuit current: 65 kA rms
Minimum required short-circuit current: 5 kA rms
Rated input cur-
rent (A)