EasyManua.ls Logo

Siemens SIMOTION CX32-2

Siemens SIMOTION CX32-2
432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
In PROFINET IO with IRT, a sync master generates a signal to which sync slaves synchronize
themselves.
Sync master and sync slaves belong to a sync domain which is assigned a name
via configuration. The role of the sync master can in principle be played by an I/O controller
as well as an I/O device. A sync domain has exactly one sync master.
Context: Sync domain and I/O systems
An important fact is that sync domains do not need to be limited to one PROFINET IO system:
The devices of several I/O systems can be synchronized by a single sync master, provided
they are connected to the same Ethernet subnet.
The following applies the other way around: An I/O system must only belong to a single sync
domain.
Signal propagation delays not negligible
For the extremely exact synchronization interval, line lengths, namely the associated delay
times, must be taken into consideration. You can use a topology editor to enter the properties
of the lines among the ports of the switches. STEP 7 uses this data and the other configuration
data to calculate the optimized process of the IRT communication and the resulting updating
time.
IRT runs in parallel to real-time and TCP/IP communication
Apart from IRT communication, for which a defined bandwidth is reserved within the update
time, RT communication and TCP/IP communication are also permitted within the update time.
With RT communication (real-time communication), the cyclic data is transferred between I/O
controller and I/O device, but without "best possible synchronism".
With non-synchronized I/O devices, data is exchanged automatically via RT communication.
Due to the fact that TCP/IP communication is also possible, other data, e.g. non-real-time data,
configuration data or diagnostic data, can be transported.
PROFINET IO controller
Typically, the function of a PROFINET IO controller is taken on by controllers (e.g. SIMOTION
C/P/D, SIMATIC S7 CPUs, ...).
The PROFINET IO controller takes on the master function for I/O data communication of the
distributed field devices. The function is comparable to a PROFIBUS DP master class 1.
PROFINET IO device
Distributed field devices such as I/Os, drives (e.g. SINAMICS S120) or operator terminals are
designated as I/O devices. The function is comparable to a PROFIBUS DP slave.
Parameter assignment / addressing
6.5 Configuring PROFINET IO
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B 145

Table of Contents

Other manuals for Siemens SIMOTION CX32-2

Related product manuals