4.7.4 Rules for the laying of PROFIBUS cables
Laying of bus cable
During laying of the PROFIBUS cable, you must:
Not twist the cable
Not stretch the cable
Not squeeze the cable
Supplementary conditions
In addition, when laying a bus cable for indoor use, you must take into account the following
supplementary conditions (dA = external cable diameter):
Table 4-6 Supplementary conditions for the laying of PROFIBUS cables
Characteristics Supplementary conditions
Bending radius for a single bend 80 mm (10xdA)
Bending radius for multiple bends 160 mm (20xdA)
Permissible temperature range for cable routing -5° C to +50° C
Temperature range for storage and stationary operation -30° C to +65° C
Additional references
Length codes for prefabricated cables can be found in:
Catalog
SIMOTION PM 21
IK PI Industrial Communication
Catalog
Connecting
4.7 Connecting PROFIBUS/MPI
SIMOTION D4x5-2
78 Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B

Table of Contents

Other manuals for Siemens SIMOTION CX32-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION CX32-2 and is the answer not in the manual?

Siemens SIMOTION CX32-2 Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION CX32-2
CategoryControl Unit
LanguageEnglish

Related product manuals