Parameter Description
p0010 = 95 Drive commissioning parameter filter
Safety Integrated commissioning
p9601 Enable functions integrated in the drive (factory setting: 0000 bin)
Functions that have been
enabled:
Functions that have been enabled:
0 hex None 80 hex STO via Power Module terminals
1 hex Basic functions via on‐
board terminals
81 hex
Basic functions via onboard terminals
STO via Power Module terminals
4 hex Extended functions via
onboard terminals
84 hex
Extended functions via onboard
terminals
STO via Power Module terminals
8 hex Basic functions via PRO‐
FIsafe
88 hex
Basic functions via PROFIsafe
STO via Power Module terminals
9 hex
Basic functions via
PROFIsafe
Basic functions via
onboard terminal
89 hex
Basic functions via PROFIsafe
Basic functions via onboard terminals
STO via Power Module terminals
C hex Extended functions via
PROFIsafe
8C hex
Extended functions via PROFIsafe
STO via Power Module terminals
D hex
Extended functions
via PROFIsafe
Basic functions via
onboard terminals
8D hex
Extended functions via PROFIsafe
Basic functions via onboard terminals
STO via Power Module terminals
p9761 Enter a password (factory setting: 0000 hex)
Permissible passwords lie in the range 1 … FFFF FFFF.
p9762 New password
p9763 Confirm password
Commissioning
5.9 Configuring safety functions and PROFIsafe using STARTER
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD 115