6.6.7 Limit value violation when SLS is active
Drive response
When motion monitoring detects a fault when SLS is active, the inverter responds by triggering
a STOP A or STOP B. The inverter response is parameterized during commissioning.
Stop responses (Page 294)
6SHHG
W
W
,QWHUQDOHYHQW
6/6DFWLYH
672DFWLYH
W
'HVHOHFW6/6
212))
)DLOVDIH
DFNQRZOHGJPHQW
6WDQGDUGDFNQRZOHGJH
5HVSRQVHFDQEHVHW
6723$RU6723%
&RQYHUWHU
LGHQWLILHVDIDXOW
*UHHQRQ
*UHHQ
RQ
5HGIODVKHVTXLFNO\
<HOORZ
RQ
<HOORZVORZ<HOORZIODVKHVTXLFNO\
/('5'<
/('6$)(
6/6
Figure 6-34 Limit value violation of safety function SLS. Example with STOP A as fault response
Inverter signal Parameter Included in the PROFI‐
safe telegram
Can be interconnec‐
ted with
F-DI F-DO
Internal event r9722.7 ---
STO active (extended functions) r9722.0 ---
SLS active r9722.4 ---
Deselect SLS r9720.4 ---
"Standard" acknowledgment p2103 --- --- ---
Fail-safe acknowledgment r9720.7 ---
ON/OFF1 r0054.0 --- --- ---
Operation
6.6 Safely Limited Speed (SLS)
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
270 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD