6.2.4 Testing the extended functions
Time
The inverter monitors as to whether the self test (= forced checking procedure, test stop) is
regularly started.
6WDUWWKHIRUFHGGRUPDQW
HUURUGHWHFWLRQRIWKH
H[WHQGHGIXQFWLRQV
0RQLWRULQJWLPHIRUWKHEDVLF
IXQFWLRQV
)RUFHGGRUPDQWHUURUSURWHFWLRQRIWKHEDVLF
IXQFWLRQVLVUHTXLUHG
6WDUWWKHIRUFHGGRUPDQWHUURUGHWHFWLRQRI
WKHEDVLFIXQFWLRQV
672LV
DFWLYH
0RQLWRULQJWLPHIRUH[WHQGHG
IXQFWLRQV
)RUFHGGRUPDQWHUURUSURWHFWLRQRIWKH
H[WHQGHGIXQFWLRQVLVUHTXLUHG
6WDUWWKHIRUFHGGRUPDQWHUURUGHWHFWLRQ
RIWKHH[WHQGHGIXQFWLRQV
$
ุ
$
7
7
Figure 6-3 Starting and monitoring the forced checking procedure (test stop)
If the inverter outputs alarm A01699 or A01697, you must initiate a forced checking procedure
at the next opportunity, e.g.:
When the system is switched on.
At specified regular intervals before the monitoring time expires.
Inverter signals Parameter Included in the PROFI‐
safe telegram
Can be interconnec‐
ted with
F-DI F-DO
STO active (basic functions) r9773.1 ---
STO cause, selection via terminal on
the Power Module
r9772.25 --- --- ---
STO active (extended functions) r9722.0 ---
Forced checking procedure (test
stop) required for the basic functions
r9773.31 --- --- ---
Forced checking procedure (test
stop) required for the extended func‐
tions
r9723.0 --- --- ---
Start forced checking procedure (ex‐
tended functions)
p9705 --- --- ---
Performing a forced checking procedure (test stop)
When testing the extended functions, the inverter switches the motor into a no-torque condition.
Operation
6.2 Regularly testing the safety functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
218 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD