5.12.2 Setting fail-safe digital inputs
5.12.2.1 Interconnecting a safety function with fail-safe digital input
Preconditions
You are online with STARTER or Startdrive.
You have selected the extended functions via onboard terminals.
Procedure with STARTER
To interconnect the fail-safe digital inputs with safety functions, proceed as follows:
1. Press the "Safety inputs/outputs" button.
2. Press the "Drive" button.
deselecte
deselecte
selected
3. If you do not use a safety function, then set the associated “Select F-DI" = "[255] statically
deselected“.
4. Interconnect the fail-safe digital inputs with the corresponding safety functions.
5. If a safety function should always be active, set the associated "Select F-DI" = "[0] Statically
active".
6. Close the screen forms.
You have assigned specific safety functions to the fail-safe digital inputs.
