5.12.5.2 Setting SS1 with acceleration monitoring
Requirement
You are online with STARTER or Startdrive.
Procedure with STARTER
To set the SS1 function with acceleration monitoring, proceed as follows:
1. Select "[3] Safety without encoder with accel_monitoring (SAM)/delay time".
2. Press the "Safe stop functions" button.
3. After the "delay time", the inverter safely switches off the motor torque – regardless of the
actual speed.
4. The "shutdown speed SS1" is a condition for the transition into the STO function.
5. The "speed tolerance" is used to track the monitoring to the actual speed.
6. The "shutdown speed acceleration monitoring" is a condition for the transition into the STO
function.
7. Close the screen form.
You have set the SS1 function with acceleration monitoring.

Commissioning
5.12 Setting extended functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
180 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD

Table of Contents