6.12.3 Selecting STO when SDI is active
Select STO
SDI is active
7KHPRWRUFRDVWVWRD
VWDQGVWLOO
6SHHG
*UHHQRQ
6',DFWLYH
<HOORZRQ<HOORZIODVKHVVORZO\
672DFWLYH
6',DFWLYH
'HVHOHFW672
'HVHOHFW6',
6',DFWLYHUHPDLQVDFWLYH
6',DFWLYHEHFRPHVLQDFWLYH
W
6',
W
W
/('5'<
/('6$)(
Inverter signals Parameter Included in the PROFI‐
safe telegram
Can be interconnected
with
F-DI F-DO
STO active (basic functions) r9773.1 ---
STO deselection (basic functions) r9773.0 ---
STO cause, selection via terminal on the Power Module r9772.25 --- --- ---
STO active (extended functions) r9722.0 ---
Deselect STO (extended functions) r9720.0 ---
SDI+ active r9722.12 ---
SDI+ deselect r9720.12 ---
SDI- active r9722.13 ---
Deselect SDI- r9720.13 ---
Operation
6.12 Selecting safety function when a safety function is active
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
306 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD