3. Set which F-DI status of the inverter is transferred via PROFIsafe status word 5 .
Note
You can transfer the status of a fail-safe digital input via PROFIsafe and simultaneously
use the same input to control a safety function.
4. Close the screen form.
You have configured the PROFIsafe telegram 900 in the inverter.
Control word 5 and status word 5 (Page 54).
Parameter Description
p9501.30 Enable F-DI in PROFIsafe telegram(Factory setting: 0 bin)
0 signal: F-DI is inhibited in the PROFIsafe telegram
1 signal: F-DI is enabled in PROFIsafe telegram
p10050 Transfer PROFIsafe F-DI (Factory setting: 0000 bin)
Bit 0 0 signal: No transfer
1 signal: PROFIsafe status word 5 transfers the status of F-DI 0
Bit 1 0 signal: No transfer
1 signal: PROFIsafe status word 5 transfers the status of F-DI 1
Bit 2 0 signal: No transfer
1 signal: PROFIsafe status word 5 transfers the status of F-DI 2
Settings for the discrepancy time and the signal filter of the fail-safe digital inputs:
Setting the filter for fail-safe digital inputs (Page 157)
Commissioning
5.9 Configuring safety functions and PROFIsafe using STARTER
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
118 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD