6. Select the "Exit safety commissioning" button.
7. Confirm the prompt for saving your settings (copy RAM to ROM).
8. Disconnect the online connection.
9. Switch off the inverter supply voltage.
10.Wait until all LEDs on the inverter go dark (no voltage condition).
11.Switch on the inverter supply voltage again.
Your settings are now active.
Parameter Description
p9700 = D0 hex SI copy function (factory setting: 0)
Start the SI parameter copy function.
p9701 = DC hex Confirm data change (factory setting: 0)
Confirm the SI basic parameter change.
p0010 = 0 Drive commissioning parameter filter
0: Ready
p0971 = 1 Save parameter
1: Save the drive object (copy from RAM to ROM)
After the inverter has saved the parameters in a non-volatile fashion, then
p0971 = 0.
Commissioning
5.10 Configuring safety functions and PROFIsafe with Startdrive
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD 125