You have set the "STO via Power Module terminals" function.
Parameter Description
p9601.7 Enable functions integrated in the drive (factory setting: 0)
1 signal: STO via the Power Module terminals has been enabled
p9650 F-DI switchover discrepancy time (Factory setting: 500 ms)
p9661 Forced checking procedure STO via PM terminals time (Factory setting: 8 h)
r9662 Forced checking procedure STO via PM terminals remaining time
r9773.30 SI status
1 signal: The forced checking procedure (test stop) for the "STO via Power Module
terminals" function is required.
Commissioning
5.11 Setting basic functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD 135