3. Press the "Safe basic functions" button:
A
$
%
&
Set the following:
(A) Set the monitoring time to the maximum value (9000 hours). This means that the
forced checking procedure monitoring for the basic functions is deactivated.
This monitoring is not required when using the extended functions, as the forced
checking procedure for the extended functions also includes the forced checking
procedure for the basic functions.
(B) Setting not required.
(C) If required, interconnected the status of the STO function, e.g. with a digital output
of your choice.
4. Close the screen form.
You have set the forced checking procedure (test stop) of the extended functions.
Commissioning
5.12 Setting extended functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
148 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD