The inverter monitors the regular forced checking procedure of the fail-safe digital output using
a time block.
You must start the forced checking procedure with a signal of your choice.
6WDUWIRUFHGFKHFNLQJ
SURFHGXUH
0RQLWRULQJWLPHIRUIDLOVDIHGLJLWDO
RXWSXW
7HVWVWRSUHTXLUHGIRUWKHGLJLWDORXWSXWV
6WDUWIRUFHGFKHFNLQJSURFHGXUHRIWKHIDLOVDIH
RXWSXW
$
7
Figure 5-16 Start and monitoring of the forced checking procedure of the fail-safe digital output
Parameter Description
p10003 Forced checking procedure timer (Factory setting: 8 h)
Setting the time to perform the forced checking procedure.
p10007 Forced checking procedure F-DO signal source (Factory setting: 0)
Select an input terminal to start the forced checking procedure.
Commissioning
5.12 Setting extended functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
168 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD