Inverter signal Parameter Included in the PROFI‐
safe telegram
Can be interconnec‐
ted with
F-DI F-DO
Ready to switch on r0052.0 --- --- ---
ON/OFF1 r0054.0 --- --- ---
Switching on the motor once SS1 is active
Procedure
To switch on the motor again once SS1 is active, proceed as follows:
1. Deselect SS1.
2. After deselecting SS1, wait until the inverter is "ready to switch on".
Alternatively: After deselecting SS1, wait a certain time before switching on. We
recommend a wait time of 200 ms.
3. Switch on the motor: ON/OFF1 = 1.
You have switched on the motor.

Operation
6.5 Safe Stop 1 (SS1)
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD 241