Switching on the motor after a discrepancy
Procedure
To switch the motor on again, proceed as follows:
1. Remove the discrepancy.
2. Acknowledge the discrepancy message with the fail-safe acknowledge signal via a fail-safe
digital input: F‑DI = 0 → 1 → 0.
Alternatively: Switch off the power supply voltage and switch on again.
3. Acknowledge the inverter with the "standard" acknowledge signal.
4. Issue an OFF1 command (ON/OFF1 = 0).
5. Switch on the motor (ON/OFF1 = 1).
You have acknowledged the discrepancy message, and switched on the motor again.

Operation
6.5 Safe Stop 1 (SS1)
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
250 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD