The feedback signal "SSM active" for pulse inhibit remains active
6WDQGVWLOO
PRQLWRULQJ
6SHHG
*UHHQ2Q
<HOORZIODVKHV
VORZO\
<HOORZRQ<HOORZRQ
672DFWLYH
6SHHGEHORZWKH
OLPLWYDOXH
'HVHOHFW672
212))
5HDG\WRVZLWFKRQ
W
/('6$)(
/('5'<
660
W
W
V
Figure 6-41 Switching on the motor when SSM is active
With this setting, you must maintain a certain sequence before switching on the motor.
Procedure
To switch the motor on, proceed as follows:
1. Select STO (or SS1) after the motor has been switched off.
2. Deselect STO (or SS1) again before you switch on the motor.
3. After deselecting STO, wait until the inverter is "ready to switch on".
Alternatively: After deselecting STO, wait a certain time before switching on. We
recommend a wait time of 200 ms.
4. Switch on motor within 5 s after deselecting STO (ON command).
You have switched on the motor.
Inverter signal Parameter Included in the PROFI‐
safe telegram
Can be interconnec‐
ted with
F-DI F-DO
STO active (extended functions) r9722.0 ---
Deselect STO (extended functions) r9720.0 ---
SSM feedback signal active (speed
below limit value)
r9722.15 ---
ON/OFF1 r0054.0 --- --- ---
Ready to switch on r0052.0 --- --- ---

Operation
6.7 Safe Speed Monitor (SSM)
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD 279