Figure A-5 Diagram 2 - acceptance test for SS1 with acceleration monitoring
Procedure
To perform the acceptance test of the SS1 function, proceed as follows:
Status
1. The inverter is ready
The inverter signals neither faults nor alarms of the safety functions
(r0945[0…7], r2122[0…7]).
SS1 is not active (r9722.1 = 0).
Go online with the STARTER and configure the following trace:
Trigger on variable - bit pattern (r9720.1 = 0)
Record the following values: r9714[0], r9714[1], r9722
Display the bits r9722.0/.1
Select the time interval and pretrigger so you can recognize the selection
of SS1 and the transition into the subsequent STO state.
Start the trace.
2. Switch on motor
2.1. Enter a speed setpoint ≠ 0.
2.2. Switch on the motor (ON command).
2.3. Check that the correct motor is running.

Appendix
A.2 Examples of acceptance tests
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
390 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD