Figure 4-9 Directly controlling the safety functions in the ET 200pro FC‑2 inverter via the F-RSM
module
SIMATIC ET 200pro FC‑2 inverters only have one internal fail-safe digital input. You require
the F‑RSM module if you wish to control the ET 200pro FC‑2 safety functions directly via a
sensor.
The F‑RSM module evaluates the sensor, and switches the "F0 rail" in the backplane bus of
the ET‑200pro system. The F0 rail selects a safety function in the inverter via the internal fail-
safe digital input.
Additional ways of installing F‑RSM module are provided in the Internet:
FAQ (
http://support.automation.siemens.com/WW/view/en/26694409)
Installing
4.4 Controlling via a fail-safe digital input
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD 65