Technical Data
B
B.1 Storage, Transport and Operation Ambient Conditions
Table B-1 General Ambient Conditions
Storage Transport Operating
CLIMATIC AMBIENT CONDITIONS
Ambient temperature +5 °C to +40 °C –25 °C to +60 °C
in accordance with
IEC 60721 3-2, Class 2K2
+5 °C to +40 °C
Relative air humidity < 95 %
(VFD must be completely dry before commissioning)
No condensation
Other climatic conditions
in accordance with class
1K3, 1Z2
in accordance with
IEC 60721-3-1
2K2
in accordance with
IEC 60721 3-2, Class 2K2
3K3
in accordance with
IEC 60721-3-3
Degree of pollution 2
without conductive pollution in accordance with
IEC 61800-5
MECHANICAL CONDITIONS*
References IEC 60721-3-2 2M1 and IEC 60721-4-2 2M1 Sine Vibration (61800-5-1)
Sine Vibration Displace‐
ment
±0.075 mm (5 to 57 Hz)
1g (57 to 150 Hz)
Random Vibration Curve 1.0 m
2
/s
3
(10 Hz -100 Hz)
-3.0 dB/octaveHz (100 Hz -200 Hz)
0.5 m
2
/s
3
(200 Hz -2000 Hz)
No
Shock 10 g No
Steady State Acceleration 3g XYZ (IEC 60721-4-2 2M1) No
Stacking No stacking permitted
Freefall No
OTHER CONDITIONS
Acceleration 5 m/s2 (9 to 200 Hz) 10 m/s2 (9 to 200 Hz)
15 m/s2 (200 to 500 Hz)
1 m/s2 (9 to 200 Hz)
Other mechanical condi‐
tions in accordance with
class
1M2
in accordance with
IEC 60721-3-1
2M1
in accordance with
IEC 60721-3-2
with exception that tilt must be
> 0 .
3M1
in accordance with
IEC 60721-3-3
OTHER AMBIENT CONDITIONS
Type 6SR5 Air-Cooled
Operating Instructions, AK, A5E39390112 105