B.3 9-Cell System Specications
Table B-4 9-Cell System Parameters
Cells in Drive
(without Redundancy)
Output Voltage
Available L-L (with O-M)
Hp Range
1
Power Cell Types
(Continuous Current Rating)
9 4000 V (4160 V) 150-6500 2Q 40A, 70A, 100A, 140A, 200A,
260A, 340A, 430A, 550A, 600A,
780A,
4Q 120A, 160A, 325A
Parameters Ratings
Input Line Voltage 2.4, 3.0, 3.3, 4.16, 4.8, 6.0, 6.3, 6.6, 6.9, 7.2, 8.4, 10, 11, 12, 12.47, 13.2, or 13.8 kV; 3-phase;
+10% / -5%A
Input Frequency 50 or 60 Hz ±5%
Input Power Factor > 0.95 above 10% load
Input Harmonics ≤ 5% TDD with ambient THDv ≤ 2%
Minimum Eciency 2Q
4
≥ 96% Total VFD → 96% Al; 96.5% Cu
Minimum Eciency 4Q
4
≥ 95.75% Total VFD → 95.75% Al; 96.25% Cu
Output Voltage 9-Cell
2300 V
3000 V
3300 V
4000 V
4160 V
Output HVF < 0.03
Output dv/dt < 3000 V/µS
Overload Capacity
1
110 % 1 minute / 10 minute
Output Frequency & Drift
2
0.5 - 330 Hz, ± 0.5 % (derates at <10 Hz and at >167 Hz)
Output Torque 10 - 167 Hz rated torque (2 - Quadrant)
Design Life 20 years
Auxiliary Voltage
3
380 V, 400 V, 415 V, 50 Hz;
460 V, 480 V, 575 V, 60 Hz; 3 - phase
Enclosure Type NEMA 1 Ventilated; (UL 50e Type 4 Non-Ventilated when M58 is selected)
Degree of Protection IP42; (UL 50e Type 4 Non-Ventilated when M58 is selected)
Ambient Temperature 0 - 40 °C (maximum 50 °C, derating starts from 40 °C on)
M58 Option Code: -45 to 45 °C (derating starts from 35 °C on)
Altitude 0 - 3300 ft. without derating (maximum 12,300 ft with derating)
Technical Data
B.3 9-Cell System Specications
Type 6SR5 Air-Cooled