WARNING
Improper device modi󹪝cations
Risk to personnel, system and environment can result from modi󹪝cations to the device,
particularly in hazardous areas.
Only carry out modi󹪝cations that are described in the instructions for the device. Failure to
observe this requirement cancels the manufacturer's warranty and the product approvals.
3.2 Use in hazardous areas
Quali󹪝ed personnel for hazardous area applications
Persons who install, connect, commission, operate, and service the device in a hazardous
area must have the following speci󹪝c quali󹪝cations:
They are authorized, trained or instructed in operating and maintaining devices and systems
according to the safety regulations for electrical circuits, high pressures, aggressive, and
hazardous media.
They are authorized, trained, or instructed in carrying out work on electrical circuits for
hazardous systems.
They are trained or instructed in maintenance and use of appropriate safety equipment
according to the pertinent safety regulations.
WARNING
Use in hazardous area
Risk of explosion.
Only use equipment that is approved for use in the intended hazardous area and labeled
accordingly.
Do not use devices that have been operated outside the conditions speci󹪝ed for hazardous
areas. If you have used the device outside the conditions for hazardous areas, make all Ex
markings unrecognizable on the nameplate.
WARNING
Loss of safety of device with type of protection "Intrinsic safety Ex i"
If the device or its components have already been operated in non-intrinsically safe circuits or
the electrical speci󹪝cations have not been observed, the safety of the device is no longer
ensured for use in hazardous areas. There is a risk of explosion.
Connect the device with type of protection "Intrinsic safety" solely to an intrinsically safe
circuit.
Observe the speci󹪝cations for the electrical data on the certi󹪝cate and/or in Technical
speci󹪝cations (Page61).
Safety notes
3.2Use in hazardous areas
SIPART PS100
Operating Instructions, 06/2023, A5E50188938-AF 17

Table of Contents

Other manuals for Siemens SIPART PS100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS100 and is the answer not in the manual?

Siemens SIPART PS100 Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS100
CategoryValve Positioners
LanguageEnglish

Related product manuals