Digital output (DO), terminals 31 and 32
Maximum supply voltage U
H
35V
"Conductive" state
Permissible rated current 50mA
Maximum terminal voltage 3V
Overload-proof
"Locked" state
"Locked" is also the status if the device is faulty or analog input
(AI) is = 0mA.
I<60µA
11.3 Rated conditions
Rated conditions
Ambient conditions for operation according to IEC60068-2 For use indoors and outdoors.
Ambient temperature
-20...+80°C (-4...+176°F)
Maximum permissible height above sea level
Up to 2000m
Relative humidity
0 ... 100%
Pollution degree according to IEC61010-1 2
Overvoltage category according to IEC61010-1 II
Enclosure degree of protection
In accordance with IEC60529
IP66
In accordance with NEMA250
Type4X
Corrosion protection according to ENISO9227 and
ENISO12944
6DR710 polycarbonate enclosure
C5‑M medium durability
6DR711 aluminum enclosure
C5‑M medium durability
Vibration resistance
Harmonic oscillations (sine) according to
IEC60068-2-6
3.5mm (0.14"), 2 ... 27Hz, 3 cycles/axis
98.1m/s² (321.84 ft/s²), 27 ... 300Hz, 3 cycles/axis
Bump (half-sine) according to
IEC60068-2-27
150m/s² (492ft/s²), 6ms, 1000 shocks/axis
Noise (controlled digitally) according to
IEC60068-2-64
10 ... 200Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axis
Climate class According to IEC/EN60721-3
Storage
1K23, -40 ... +80°C (-40 ... +176°F)
Transport
2K13, -40 ... +80°C (-40 ... +176°F)