Service and maintenance
10
10.1 Basic safety notes
10.1.1 Maintenance
The device is maintenance-free. However, a periodic inspection according to pertinent directives
and regulations must be carried out.
An inspection can include, for example, check of:
Ambient conditions
Seal integrity of the process connections, cable entries, and cover
Reliability of power supply, lightning protection, and grounds
WARNING
Dust layers above 5 mm
Risk of explosion in hazardous areas.
Device may overheat due to dust build up.
Remove dust layers in excess of 5mm.
NOTICE
Penetration of moisture into the device
Damage to device.
Make sure when carrying out cleaning and maintenance work that no moisture penetrates
the inside of the device.
10.2 Cleaning
Cleaning the enclosure
Clean the outside of the enclosure with the inscriptions and the display window using a cloth
moistened with water or a mild detergent.
Do not use any aggressive cleansing agents or solvents, e.g. acetone. Plastic parts or the
painted surface could be damaged. The inscriptions could become unreadable.