No. Information Type of
Informa-
tion
Comments
10231 U</> ACTIVE OUT Over-/Under-Voltage protection is ACTIVE
10240 Uph-e> Pickup OUT Uph-e> Pickup
10241 Uph-e>> Pickup OUT Uph-e>> Pickup
10242 Uph-e>(>) PU L1 OUT Uph-e>(>) Pickup L1
10243 Uph-e>(>) PU L2 OUT Uph-e>(>) Pickup L2
10244 Uph-e>(>) PU L3 OUT Uph-e>(>) Pickup L3
10245 Uph-e> TimeOut OUT Uph-e> TimeOut
10246 Uph-e>> TimeOut OUT Uph-e>> TimeOut
10247 Uph-e>(>) TRIP OUT Uph-e>(>) TRIP command
10248 Uph-e> PU L1 OUT Uph-e> Pickup L1
10249 Uph-e> PU L2 OUT Uph-e> Pickup L2
10250 Uph-e> PU L3 OUT Uph-e> Pickup L3
10251 Uph-e>> PU L1 OUT Uph-e>> Pickup L1
10252 Uph-e>> PU L2 OUT Uph-e>> Pickup L2
10253 Uph-e>> PU L3 OUT Uph-e>> Pickup L3
10255 Uphph> Pickup OUT Uph-ph> Pickup
10256 Uphph>> Pickup OUT Uph-ph>> Pickup
10257 Uphph>(>)PU L12 OUT Uph-ph>(>) Pickup L1-L2
10258 Uphph>(>)PU L23 OUT Uph-ph>(>) Pickup L2-L3
10259 Uphph>(>)PU L31 OUT Uph-ph>(>) Pickup L3-L1
10260 Uphph> TimeOut OUT Uph-ph> TimeOut
10261 Uphph>> TimeOut OUT Uph-ph>> TimeOut
10262 Uphph>(>) TRIP OUT Uph-ph>(>) TRIP command
10263 Uphph> PU L12 OUT Uph-ph> Pickup L1-L2
10264 Uphph> PU L23 OUT Uph-ph> Pickup L2-L3
10265 Uphph> PU L31 OUT Uph-ph> Pickup L3-L1
10266 Uphph>> PU L12 OUT Uph-ph>> Pickup L1-L2
10267 Uphph>> PU L23 OUT Uph-ph>> Pickup L2-L3
10268 Uphph>> PU L31 OUT Uph-ph>> Pickup L3-L1
10270 3U0> Pickup OUT 3U0> Pickup
10271 3U0>> Pickup OUT 3U0>> Pickup
10272 3U0> TimeOut OUT 3U0> TimeOut
10273 3U0>> TimeOut OUT 3U0>> TimeOut
10274 3U0>(>) TRIP OUT 3U0>(>) TRIP command
10280 U1> Pickup OUT U1> Pickup
10281 U1>> Pickup OUT U1>> Pickup
10282 U1> TimeOut OUT U1> TimeOut
10283 U1>> TimeOut OUT U1>> TimeOut
10284 U1>(>) TRIP OUT U1>(>) TRIP command
10290 U2> Pickup OUT U2> Pickup
10291 U2>> Pickup OUT U2>> Pickup
10292 U2> TimeOut OUT U2> TimeOut
10293 U2>> TimeOut OUT U2>> TimeOut
10294 U2>(>) TRIP OUT U2>(>) TRIP command
10300 U1< Pickup OUT U1< Pickup
Functions
2.5 Under and over-voltage protection (optional)
SIPROTEC 4, 7VK61, Manual 113
C53000-G1176-C159-5, Edition 05.2018

Table of Contents