voltage of the switched feeder. This setting does not apply for a close command via the integrated control
functions. If the synchronism check is desired, the device must either feature the integrated synchronism
check function or an external device for synchronism check must be connected.
If the internal synchronism check is to be used, the synchronism check function must be enabled; an addi-
tional voltage U
sy2
for synchronism check has to be connected to the device and this must be correctly para-
meterised in the Power System Data 1 (address 210 U4 transformer = Usy2 transf. and the associated
factors).
If no synchronism check is to be performed with manual closing, set MAN. CLOSE = w/o Sync-check. If a
check is desired, set with Sync-check. To not use the MANUAL CLOSE function of the device, set MAN.
CLOSE to NO. This may be reasonable if the close command is output to the circuit breaker without involving
the 7VK61, and the relay itself is not desired to issue a close command.
For commands via the integrated control (on site, DIGSI, serial interface) address 1152 Man.Clos. Imp.
determines whether a close command via the integrated control regarding the MANUAL CLOSE handling for
the protection functions (like instantaneous re-opening when switching onto a fault) is to act like a MANUAL
CLOSE command via binary input. This address also informs the device to which switchgear this applies. You
can select from the switching devices which are available to the integrated control. Select the circuit breaker
which operates for manual closure and, if required, for automatic reclosure (usually Q0). If none is set here, a
CLOSE command via the control will not generate a MANUAL CLOSE impulse for the protection function.
Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter C Setting Options Default Setting Comments
1103 FullScaleVolt. 1.0 .. 1200.0 kV 400.0 kV Measurement: Full Scale
Voltage (100%)
1104 FullScaleCurr. 10 .. 5000 A 1000 A Measurement: Full Scale
Current (100%)
1107 P,Q sign not reversed
reversed
not reversed P,Q operational measured
values sign
1130A PoleOpenCurrent 1A 0.05 .. 1.00 A 0.10 A Pole Open Current
Threshold
5A 0.25 .. 5.00 A 0.50 A
1131A PoleOpenVoltage 2 .. 70 V 30 V Pole Open Voltage
Threshold
1135 Reset Trip CMD CurrentOpenPole
Current AND CB
Pickup Reset
CurrentOpenPole RESET of Trip Command
1136 OpenPoleDetect. OFF
Current AND CB
w/ measurement
w/ measurement open pole detector
1150A SI Time Man.Cl 0.01 .. 30.00 sec 0.30 sec Seal-in Time after MANUAL
closures
1151 MAN. CLOSE with Sync-check
w/o Sync-check
NO
NO Manual CLOSE COMMAND
generation
1152 Man.Clos. Imp. (Einstellmöglichkeiten
anwendungsabhängig)
none MANUAL Closure Impulse
after CONTROL
2.1.5.2
Functions
2.1 General
SIPROTEC 4, 7VK61, Manual 39
C53000-G1176-C159-5, Edition 05.2018