The trip circuit supervision does not operate during system faults. A momentary closed tripping contact does
not lead to a fault indication. If, however, other trip relay contacts from different devices are connected in
parallel in the trip circuit, the fault indication must be delayed by Alarm Delay (see also Figure 2-62). After
clearance of the failure in the trip circuit, the fault message automatically resets with the same time delay.
[logikdiagramm-auskruebrwchg-1-be-wlk-310702, 1, en_GB]
Figure 2-62 Logic diagram for trip circuit supervision with one binary input
Setting Notes
General
The number of circuits to be supervised was set during the configuration in address 140 Trip Cir. Sup.
(Section 2.1.1.2 Setting Notes). If the trip circuit supervision is not used at all, the setting Disabled must be
applied there.
The trip circuit supervision can be switched in address 4001 FCT TripSuperv. ON- or OFF. The number of
binary inputs that shall be used in each of the supervised circuits is set in address 4002 No. of BI. If the
routing of the required binary inputs does not comply with the selected monitoring mode, an alarm is issued
(
TripC ProgFAIL...
with identification of the non-compliant circuit).
Supervision with one binary input
The alarm for supervision with two binary inputs is always delayed by approx. 1s to 2s, whereas the delay time
of the alarm for supervision with one binary input can be set in address 4003 Alarm Delay. If only the
device 7VK61 is connected to the trip circuits 1 s to 2 s are sufficient, as the trip circuit supervision does not
operate during a system fault. If, however, trip contacts from other devices are connected in parallel in the trip
circuit, the alarm must be delayed such that the longest trip command duration can be reliably bridged.
Settings
Addr.
Parameter Setting Options Default Setting Comments
4001 FCT TripSuperv. ON
OFF
OFF TRIP Circuit Supervision is
4002 No. of BI 1 .. 2 2 Number of Binary Inputs per trip
circuit
4003 Alarm Delay 1 .. 30 sec 2 sec Delay Time for alarm
Information List
No.
Information Type of
Informa-
tion
Comments
6854 >TripC1 TripRel SP >Trip circuit superv. 1: Trip Relay
6855 >TripC1 Bkr.Rel SP >Trip circuit superv. 1: Breaker Relay
6856 >TripC2 TripRel SP >Trip circuit superv. 2: Trip Relay
6857 >TripC2 Bkr.Rel SP >Trip circuit superv. 2: Breaker Relay
6858 >TripC3 TripRel SP >Trip circuit superv. 3: Trip Relay
6859 >TripC3 Bkr.Rel SP >Trip circuit superv. 3: Breaker Relay
6861 TripC OFF OUT Trip circuit supervision OFF
6865 FAIL: Trip cir. OUT Failure Trip Circuit
6866 TripC1 ProgFAIL OUT TripC1 blocked: Binary input is not set
2.7.2.2
2.7.2.3
2.7.2.4
Functions
2.7 Monitoring Functions
SIPROTEC 4, 7VK61, Manual 147
C53000-G1176-C159-5, Edition 05.2018