EasyManua.ls Logo

Siemens SIPROTEC 4 7VK61 - Overcurrent Protection

Siemens SIPROTEC 4 7VK61
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Overcurrent protection (optional)
The device 7VK61 features a time overcurrent protection function with four independent stages that can be
combined freely with one another.
General
The overcurent protection has a total of 4 stages for each phase current and four stages for the earth current,
these are:
2 overcurrent stages with a definite time characteristic (O/C with DT),
1 overcurrent stage with inverse time characteristic (IDMT),
1 additional overcurrent stage which is preferably used as a stub protection, but which can be applied as
an additional normal definite time delayed stage. With the device variants for the region Germany (10th
digit of ordering code = A) this stage is only available if the setting 126 TOC IEC /w 3ST is active.
These 4 stages are independent from each other and are freely combinable. Blocking by external criteria via
binary input is possible as well as rapid (non-delayed) tripping (e.g. by an external automatic reclose device).
During energization of the protected feeder onto a dead fault it is also possible to release any stage, or also
several, for non-delayed tripping. If you do not need all stages, each individual stage can be deactivated by
setting the pickup threshold to ∞.
Functional Description
Measured Values
The phase currents are fed to the device via the input transformers of the measuring input. Earth current 3·Ι
0
is either measured directly or calculated depending on the ordered device version and usage of the fourth
current input Ι
4
of the device.
If Ι
4
is connected to the starpoint of the current transformer set, the earth current will be available directly as
measured quantity.
If the fourth current input Ι
4
is not connected as earth current transformer, the device will calculate the earth
current from the phase currents. This requires, of course, all three phase currents from a set of three star-
connected current transformers to be available and connected to the device.
Definite time high set current stage Ι>>
Each phase current is compared with the setting value Iph>> (address 2610) the earth current is compared
with 3I0>> PICKUP (address2612). A trip command is issued after pickup of an element and expiration of
the associated time delays T Iph>> (address 2611) or T 3I0>> (address 2613). The dropout value is about
7 % below the pickup value, but at least 1,8 % of the rated current.
The figure below shows the logic diagram of the Ι stages. They can be blocked via binary input
>BLOCK O/C
I>>
. The binary input
>O/C InstTRIP
and the function block “switch-onto-fault” are common to all stages
and described below. They may, however, separately affect the phase and/or ground current elements. This is
accomplished with the following setting parameters:
I>> InstTrip BI (Address 2614) determines whether a non-delayed trip of this element via binary
input
>O/C InstTRIP
is possible (YES) or not possible (NO) and
I>> SOTF (address2615) whether during switching onto a fault tripping shall be instantaneous (YES) or
not (NO).
2.3
2.3.1
2.3.2
Functions
2.3 Overcurrent protection (optional)
SIPROTEC 4, 7VK61, Manual 69
C53000-G1176-C159-5, Edition 05.2018

Table of Contents

Related product manuals