Addr. Parameter Setting Options Default Setting Comments
3764 Uph-ph<< 1.0 .. 175.0 V 17.0 V Uph-ph<< Pickup
3765 T Uphph<< 0.00 .. 100.00 sec 1.00 sec T Uph-ph<< Time Delay
3768 CURR.SUP.Uphph< ON
OFF
ON Current supervision (Uph-ph)
3769A Uphph<(<) RESET 1.01 .. 1.20 1.05 Uph-ph<(<) Reset ratio
3771 U1<(<) OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF Operating mode U1 undervoltage
prot.
3772 U1< 1.0 .. 100.0 V 30.0 V U1< Pickup
3773 T U1< 0.00 .. 100.00 sec 2.00 sec T U1< Time Delay
3774 U1<< 1.0 .. 100.0 V 10.0 V U1<< Pickup
3775 T U1<< 0.00 .. 100.00 sec 1.00 sec T U1<< Time Delay
3778 CURR.SUP.U1< ON
OFF
ON Current supervision (U1)
3779A U1<(<) RESET 1.01 .. 1.20 1.05 U1<(<) Reset ratio
Information List
No. Information Type of
Informa-
tion
Comments
234.2100 U<, U> blk IntSP U<, U> blocked via operation
10201 >Uph-e>(>) BLK SP >BLOCK Uph-e>(>) Overvolt. (phase-earth)
10202 >Uph-ph>(>) BLK SP >BLOCK Uph-ph>(>) Overvolt (phase-phase)
10203 >3U0>(>) BLK SP >BLOCK 3U0>(>) Overvolt. (zero sequence)
10204 >U1>(>) BLK SP >BLOCK U1>(>) Overvolt. (positive seq.)
10205 >U2>(>) BLK SP >BLOCK U2>(>) Overvolt. (negative seq.)
10206 >Uph-e<(<) BLK SP >BLOCK Uph-e<(<) Undervolt (phase-earth)
10207 >Uphph<(<) BLK SP >BLOCK Uphph<(<) Undervolt (phase-phase)
10208 >U1<(<) BLK SP >BLOCK U1<(<) Undervolt (positive seq.)
10215 Uph-e>(>) OFF OUT Uph-e>(>) Overvolt. is switched OFF
10216 Uph-e>(>) BLK OUT Uph-e>(>) Overvolt. is BLOCKED
10217 Uph-ph>(>) OFF OUT Uph-ph>(>) Overvolt. is switched OFF
10218 Uph-ph>(>) BLK OUT Uph-ph>(>) Overvolt. is BLOCKED
10219 3U0>(>) OFF OUT 3U0>(>) Overvolt. is switched OFF
10220 3U0>(>) BLK OUT 3U0>(>) Overvolt. is BLOCKED
10221 U1>(>) OFF OUT U1>(>) Overvolt. is switched OFF
10222 U1>(>) BLK OUT U1>(>) Overvolt. is BLOCKED
10223 U2>(>) OFF OUT U2>(>) Overvolt. is switched OFF
10224 U2>(>) BLK OUT U2>(>) Overvolt. is BLOCKED
10225 Uph-e<(<) OFF OUT Uph-e<(<) Undervolt. is switched OFF
10226 Uph-e<(<) BLK OUT Uph-e<(<) Undervolt. is BLOCKED
10227 Uph-ph<(<) OFF OUT Uph-ph<(<) Undervolt. is switched OFF
10228 Uph-ph<(<) BLK OUT Uphph<(<) Undervolt. is BLOCKED
10229 U1<(<) OFF OUT U1<(<) Undervolt. is switched OFF
10230 U1<(<) BLK OUT U1<(<) Undervolt. is BLOCKED
2.5.5
Functions
2.5 Under and over-voltage protection (optional)
112 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018