Siemens SIPROTEC 4 7VK61 - Information List

Siemens SIPROTEC 4 7VK61
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addr. Parameter Setting Options Default Setting Comments
3764 Uph-ph<< 1.0 .. 175.0 V 17.0 V Uph-ph<< Pickup
3765 T Uphph<< 0.00 .. 100.00 sec 1.00 sec T Uph-ph<< Time Delay
3768 CURR.SUP.Uphph< ON
OFF
ON Current supervision (Uph-ph)
3769A Uphph<(<) RESET 1.01 .. 1.20 1.05 Uph-ph<(<) Reset ratio
3771 U1<(<) OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF Operating mode U1 undervoltage
prot.
3772 U1< 1.0 .. 100.0 V 30.0 V U1< Pickup
3773 T U1< 0.00 .. 100.00 sec 2.00 sec T U1< Time Delay
3774 U1<< 1.0 .. 100.0 V 10.0 V U1<< Pickup
3775 T U1<< 0.00 .. 100.00 sec 1.00 sec T U1<< Time Delay
3778 CURR.SUP.U1< ON
OFF
ON Current supervision (U1)
3779A U1<(<) RESET 1.01 .. 1.20 1.05 U1<(<) Reset ratio
Information List
No. Information Type of
Informa-
tion
Comments
234.2100 U<, U> blk IntSP U<, U> blocked via operation
10201 >Uph-e>(>) BLK SP >BLOCK Uph-e>(>) Overvolt. (phase-earth)
10202 >Uph-ph>(>) BLK SP >BLOCK Uph-ph>(>) Overvolt (phase-phase)
10203 >3U0>(>) BLK SP >BLOCK 3U0>(>) Overvolt. (zero sequence)
10204 >U1>(>) BLK SP >BLOCK U1>(>) Overvolt. (positive seq.)
10205 >U2>(>) BLK SP >BLOCK U2>(>) Overvolt. (negative seq.)
10206 >Uph-e<(<) BLK SP >BLOCK Uph-e<(<) Undervolt (phase-earth)
10207 >Uphph<(<) BLK SP >BLOCK Uphph<(<) Undervolt (phase-phase)
10208 >U1<(<) BLK SP >BLOCK U1<(<) Undervolt (positive seq.)
10215 Uph-e>(>) OFF OUT Uph-e>(>) Overvolt. is switched OFF
10216 Uph-e>(>) BLK OUT Uph-e>(>) Overvolt. is BLOCKED
10217 Uph-ph>(>) OFF OUT Uph-ph>(>) Overvolt. is switched OFF
10218 Uph-ph>(>) BLK OUT Uph-ph>(>) Overvolt. is BLOCKED
10219 3U0>(>) OFF OUT 3U0>(>) Overvolt. is switched OFF
10220 3U0>(>) BLK OUT 3U0>(>) Overvolt. is BLOCKED
10221 U1>(>) OFF OUT U1>(>) Overvolt. is switched OFF
10222 U1>(>) BLK OUT U1>(>) Overvolt. is BLOCKED
10223 U2>(>) OFF OUT U2>(>) Overvolt. is switched OFF
10224 U2>(>) BLK OUT U2>(>) Overvolt. is BLOCKED
10225 Uph-e<(<) OFF OUT Uph-e<(<) Undervolt. is switched OFF
10226 Uph-e<(<) BLK OUT Uph-e<(<) Undervolt. is BLOCKED
10227 Uph-ph<(<) OFF OUT Uph-ph<(<) Undervolt. is switched OFF
10228 Uph-ph<(<) BLK OUT Uphph<(<) Undervolt. is BLOCKED
10229 U1<(<) OFF OUT U1<(<) Undervolt. is switched OFF
10230 U1<(<) BLK OUT U1<(<) Undervolt. is BLOCKED
2.5.5
Functions
2.5 Under and over-voltage protection (optional)
112 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018